A single‑phase AC load consumes P=4 kW at V=400 V rms, f=50 Hz, with lagging power factor cos = 0.65. A capacitor is connected in parallel with the load to bring PF to unity. What capacitance should be used?
Answer
93 μF
The correct answer is 93 μF — Convert to microfarads: 9.3\,F=93\,.
Step-by-step solution
- Find the power factor angle from cos=0.65.(0.65).5.
- Compute the tangent: tan/0.65.169.
- Calculate reactive power Q=P=4000\,W.169\,var.
- Determine angular frequency =2 f=2=314.16\,.
- Use the relation for capacitor reactive power Q_c= C to cancel Q: set Q_c=Q.
- Solve for C: C=Q/()=4676/(.16).3\,F.
- Convert to microfarads: 9.3\,F=93\,.
Common mistake: Using V^2/ instead of to compute C
Concept tested: Power factor correction with capacitor