A single‑phase AC load consumes at a rms voltage and frequency . The load has a lagging power factor . A capacitor is connected in parallel with the load to improve the overall power factor to unity. Determine the required capacitance (in ) and state the rms current drawn from the source after correction.

hard 5 marks Class 12 · Physics · Alternating Current
Answer
Required capacitance ; corrected rms current

The correct answer is Required capacitance ; corrected rms current — After power‑factor correction, the current is purely real: .

Step-by-step solution

  1. Calculate the apparent power before correction: .
  2. Find the initial reactive power: (lagging).
  3. To achieve unity power factor, the capacitor must supply an equal magnitude of reactive power: (capacitive).
  4. Use the formula with :
  5. .
  6. Convert to microfarads: .
  7. After power‑factor correction, the current is purely real: .
Common mistake: Using peak voltage instead of rms voltage in the reactive‑power formula

Concept tested: Power‑factor correction using a capacitor