A single‑phase load consumes at , and has a lagging power factor of . To improve the power factor to unity, a capacitor is connected in parallel with the load. What capacitance should be used?\n\nA) \nB) \nC) \nD)

hard MCQ 3 marks Class 12 · Physics · Alternating Current
  1. 120 \muF
  2. 184 \muF
  3. 250 \muF
  4. 320 \muF
Answer
184 \muF

The correct answer is 184 \muF — The correct option is (B) .

Step-by-step solution

  1. Apparent power .
  2. Reactive power supplied by the load: .
  3. Calculate .
  4. Hence (lagging).
  5. To obtain unity power factor the capacitor must supply an equal leading reactive power: .
  6. For a capacitor , where .
  7. Solve for : .
  8. Compute denominator: , .
  9. Thus .
  10. Convert to microfarads: .
  11. The correct option is (B) .
Common mistake: Using instead of ; forgetting the term.

Concept tested: Power factor correction with capacitor